Black banner

DG200-2 (3 phase)

DG200-2 (3 phase)

Caterpillar is leading the power generation marketplace with Power Solutions engineered to deliver unmatched flexibility, expandability, reliability, and cost-effectiveness.

Generator Set Specifications

Frequency

60 Hz

Natural Gas Rating

200 eKW

Emissions/Fuel Strategy

U.S. EPA Certified for Non-Emergency Application

Displacement

864.71in

Fuel Type

Natural Gas

Speed

1800 rpm

Engine Specifications

Engine Model

14.2 L, Inline 6, 4 Cycle, Spark - Ignited

Fuel System

Carburetor, Down Draft

Aspiration

Turbocharged-Aftercooled

Governor Type

Electronic

Compression Ratio

9.5:1

Bore

5.31in

Stroke

6.5in

Generator Set Dimensions

Length

127.95in

Width

52.93in

Height

67.37in

Weight

5756lb

Standard Equipment:

  • Cooling
    • Closed coolant recovery system
    • Factory-installed radiator
    • 50/50 Ethylene glycol antifreeze
    • Radiator and cooling fan complete with protective guards
    • Standard ambient temperatures up to 50°C (122°F)
  • Air Inlet
    • Single element air filter
  • Fuel
    • Primary and secondary fuel shut-off
    • Low fuel pressure switch
    • Fuel pressure test po
    • Natural Gas or LP Vapor
    • NPT connection
    • Dual lock off valves
  • Exhaust
    • Exhaust outlet with 3” pipe
  • Generator
    • Permanent magnet excitation
    • Full load capacity alternator
    • Class H insulation material
    • Permanent magnet excitation
    • Integrated Voltage Regulator
    • Matched to the performance and output characteristics of Cat engines
    • Class H insulation material
    • Full load capacity alternator
    • IP23 Protection
  • Controls
    • EMCP 4.2 Series generator set controller
  • Mounting
    • Vibration isolaton (puck type)
    • Rubber vibration isolators
  • Electric Power - Package Serial Number Prefix
    • Battery charging alternator
  • Electric Starting And/or Prelube
    • Battery cables
    • Solenoid activated starter motor
    • Engine electrical system
    • Solenoid activated starter motor
  • Governor
    • Electronic governor (non adjustable)
  • Control Panel
    • EMCP 4.2 Series generator set controller
  • Starting/charging
    • Batteries with rack and cables
    • 12 volt starting motor

Optional Equipment:

  • Starting/charging
    • Jacket water heater
    • Battery heater
    • Charging alternator
    • Battery charger – UL Listed 10 amp
  • General
    • Enclosures: sound attenuated, weather protective
    • Suitable for Use as Service Equipment (SUSE)
    • Automatic transfer switches (ATS)
    • UL 2200 package
    • CSA Certification
  • Generator
    • Thermal magnetic or electronic trip MCCBs
    • Anti-condensation heater
    • Shunt trip and auxiliary contact breaker
    • Anti-condensation heater
    • Excitation: [ ] Permanent Magnet Excited (PM)
    • Oversize and premium generators

Contact Us

Get A Quote

Thank you for your interest in Mustang Cat. We are here to help you in any way that we can. If you have a question, need equipment advice or just need additional information, we want to hear from you. You can email, phone or fill out the form below and we will be happy to connect with you.

    true I agree to all the terms and conditions

    This site is protected by reCAPTCHA and the Google Privacy Policy and Terms of Service apply.