Black banner

Cat C32 Generator Set

Cat C32 Generator Set

C32 generator sets incorporate a separate circuit aftercooling system (SCAC) for all configurations. The primary advantage of the SCAC systsem is reduced aftercooler corrosion since no sea water circulates through the aftercooler. Many other improvements on these engines contribute to minimizing owning and operating costs. The EPA Tier 4, IMO II/IMO III switchable and EU Stage 5 compliant ratings are available with heat exchanger or keel cooled options. Heat exchanger configurations have an optional front mounted sea water pump.

Power Rating

Power Range

550 - 940 ekW

Generator Set Specifications

Frequency

50 / 60

Emissions/Fuel Strategy

EPA Tier 4, IMO II/IMO III switchable and EU Stage 5

Minimum Rating

500 ekW (913 kVA)

Maximum Rating

940 ekW (1175 kVA)

Speed

1500 / 1800 rpm

Engine Specifications

Aspiration

Turbocharged and aftercooled

Bore

5.7in

Stroke

6.38in

Displacement

1959in³

Governor Type

Electronic

Fuel System

MEUI

Engine Model

V 12, 4-stroke-Cycle-Diesel

Generator Specifications

Excitation

Permanent magnet

Number of Poles

4

Number of Bearings

2 roller bearings

Number of Leads

6

Insulation

Class H

IP Rating

23

Voltage Regulator

CDVR

Generator Set Dimensions

Width

60.2in

Height

65.6in

Weight - Estimated

15721lb

Length

162.8 in/4271 mm (minimum), 175.3 in/4452 mm (maximum)

Standard Equipment:

  • Air Inlet System
    • Separate circuit after-cooled (SCAC)
    • Turbocharger, jacket water cooled
    • Turbocharger inlet, 152 mm (6 in) OD straight connection
  • Control System
    • If an EMCP panel or MGCP option is not chosen as optional equipment, then start/stop controls must be provided by the customer
    • Electronic diagnostics and fault logging
    • Engine Protection Mode for extended ambient conditions
    • Electronic fuel/air ratio control
  • Cooling System
    • Separate Circuit After-Cooling (SCAC) for Heat Exchanged (HEX) & Keel cooled engines
    • Jacket Water (JW) and SCAC Heat Exchangers Shell & Tube for HEX cooled engines
    • SCAC pump, gear driven
    • Jacket water pump, gear driven
    • Sea water pump, bronze impeller, gear driven, for HEX cooled engines only
    • Jacket water HEX with Sea water pump Connections: 76.2 mm (3in) ID Standard
    • 4 Bolt ANSI Flange Connection
    • Jacket water HEX without Sea water pump Connection: 2.5" hose barb connection (inlet), 76.2 mm (3in) ID Standard 4 Bolt ANSI Flange (outlet)
    • Keel Connections: 76.2 mm (3in) ID Standard 4 Bolt ANSI Flange Connection
    • SCAC and JW shunt tanks for maintaining proper Pump inlet pressures
  • Exhaust System
    • Water-cooled exhaust manifold & turbocharger
    • 4 Bolt 130 mm (5.12 in) diameter flanged outlet
  • Flywheels & Flywheel Housings
    • Flywheel Housing, SAE No. 0
    • Flywheel, 18 inch, 136 teeth
    • SAE standard rotation
  • Fuel System
    • Duplex Fuel Filters, Spin-on, RH service
    • Fuel connections size: Supply JIC 37 Deg -10 (7/8-14), Return JIC 37 Deg -8 (3/4-16)
    • Plate-type fuel cooler installed behind Aftercooler Shunt Tank
    • Fuel transfer pump, gear driven
    • Manual fuel priming pump
  • Generators And Generator Attachments
    • SR5 form wound
    • 2 roller bearings
    • Permanent magnet excitation
    • 4 pole, 6 leads, Series Star connected
    • Caterpillar's Digital Voltage Regulator (CDVR)
    • Marine Class H insulation, Class F temperature rise
    • Surface mounted platinum (PT100) 3-wire RTDs, 2 per phase on stator and one each on support bearings
    • Anti-condensation space heaters (2 elements - 240 VAC, 1000 Watts
    • IP23 Protection suitable for use with Fixed Water Based Local Application Fire Fighting Systems (FWBLAFFS)
    • System IV insulation for harsh environment protection
  • Lube System
    • Simplex oil filters, RH service
    • Deep sump oil pan
    • RH service oil filler locations
    • RH service dipstick
    • Oil pump, gear driven
  • Mounting System
    • Formed C-channel rails, 300mm (11.81in) height
    • Six shipped loose combined helical spring/rubber
    • isolators for installation below package base
  • General
    • Front Damper guard
    • Common electrical bondng point on HEX and KEEL cooled engines

Optional Equipment:

  • Alarm And Protection
    • Remote panels
    • MCS Controller
    • Power analyzer module
    • Oil level, exhaust temperature, air starting pressure, heat exchanger pressure sensors
  • Exhaust System
    • Dry Elbows
    • Flexible Fitting
    • Flange
    • Muffler
    • Muffler Spark Arresting
    • Rain Cap
  • Air Inlet System
    • Air Inlet Cleaner
    • Closed Crankcase Ventilation
    • Air inlet adapter
  • Charging System
    • Battery Chargers, Charging Alternators
  • Control System
    • Load Sharing Attachment
  • Fuel System
    • Water Separator
  • Lube System
    • Duplex Oil Filters, Sump Pump
  • Protection System
    • Fuel and Oil Shielding
  • Starting System
    • Electric Starting Motors - Single 24 Volt
    • Air Starting Motor
    • Dual Starting Motors (Electric and Air)
    • Air Start Accessories
    • Starting Aids - JW Heaters
    • Battery Sets - 24 Volt - Dry

Contact Us